Harmonik

Power Quality in the German Transmission System — Large-Scale Monitoring, Correlation Analysis, and Long-Term Forecasting

85 IEC 61000-4-30 Class A monitoring sites across 50 substations in the German transmission system — 38 bei 110 kV, 21 bei 220 kV, 26 bei 380 kV. Hierarchical clustering reveals which sites are redundant and which are uniquely informative. Ensemble forecasting of weekly 95th-percentile PQ parameters outperforms any individual model. The first dataset to demonstrate systematic, recurring PQ correlation structures at transmission level driven by inverter-based generation.

KI-Rechenzentren und Stromqualität – eine neue Kategorie von Netzstörungen

AI training clusters create a load type that did not exist when power quality standards were written: synchronised GPU operation producing oscillatory load signatures with 10+ MW/second ramps, harmonic THD exceeding 5%, and simultaneous UPS disconnection risk of 2+ GW in dense data centre corridors. A real Dominion Energy grid event was triggered by a data centre producing a voltage sag at precisely once per second. Three open-access papers from 2025–2026 document the scale of the problem and the mitigation approaches now being required by grid operators.

Power Quality in an Academic Institution’s Electrical Distribution System — Sultan Qaboos University

Full campus PQ audit at Sultan Qaboos University, Oman — 33 kV/11 kV/415 V distribution system. Non-linear loads: PV inverters, USV-Systeme, VFD chillers, and hundreds of switch-mode power supplies in computer labs. THDI ranged from 2–10%, TDD from 2–8% across measurement points. Main substations compliant with IEEE 519 due to harmonic aggregation cancellation — but individual buildings exceeded 8% at peak load. Key lesson: the THD vs. TDD distinction prevents false alarms. The study establishes a pre-DER baseline before planned large-scale PV integration.

EV Charging and Power Quality in LV Residential Networks — From Individual Charger to Fleet Penetration

Level 2 EV chargers at 7.2 kW produce third-harmonic dominant current that accumulates in the neutral conductor and causes voltage unbalance increasing with distance from the transformer. Monte Carlo simulation across multiple penetration levels shows uncontrolled charging at 30%+ penetration can push VUF beyond 2% at feeder end buses. Smart charging eliminates the problem without hardware mitigation. EV chargers also produce supraharmonic emissions (2–150 kHz) that can disrupt the PLC communications intended to manage EV charging itself.

Data-Driven Power Quality Evaluation in a Hospital Electrical System

Full PQ audit at University of Lampung Hospital, Indonesien. Voltage and frequency compliant at the meter — but current TDD exceeded IEEE 519 limits many times over, voltage unbalance non-compliant, power factor lagging. All problems originated inside the facility from non-linear loads: SMPS, UPS, VFD, imaging equipment.

Power Quality Issues in Medical Facilities — EKG Malfunction

A hospital EKG machine produced unreliable results. Signal wiring routed parallel to the power cord created inductive coupling — a classic internal EMC failure invisible to utility PQ standards. Root cause: wiring practice, not utility supply quality. 75% of medical facility PQ problems are internal wiring and grounding issues.

Erstaunlicher Intl – Generators and Nonlinear Loads: How Harmonic Mitigation Eliminates the Oversizing Requirement

Mirus International demonstrates that generators feeding non-linear loads must be derated or oversized to prevent excessive voltage distortion — standard practice adds 20–25% generator capacity. The Wide Spectrum Filter (Lineator) eliminates the oversizing requirement by reducing harmonic current drawn from the generator, enabling right-sized generator selection and significant capital and fuel savings.

Erstaunlicher Intl – Sinewave Filter vs. dV/dT Filter for Long-Cable VFD Applications: A Head-to-Head Field Comparison

Long cable VFD applications produce cable resonance that amplifies dV/dt at the motor terminals — causing insulation stress and premature motor failure. A dV/dt filter limits the voltage rise rate but does not produce a true sine wave. A sinewave filter eliminates both the resonance and the harmonic content. Field comparison at San Antonio Water Authority shows measured motor terminal voltage for both filter types.

Erstaunlicher Intl – Turbo Blower Efficiency and Harmonic Compliance at a Municipal Wastewater Plant

Municipal wastewater plant with turbo blower VFDs: total harmonic current distortion exceeded IEEE 519 limits at the point of common coupling. Three-party solution — utility, municipality, and Mirus — achieved ITDD (Individual Total Demand Distortion) compliance using Lineator filters. Efficiency improved and the plant qualified for utility incentives unavailable under non-compliant harmonic conditions.

Erstaunlicher Intl – Harmonic Compliance for Nine Panamax Bulk Carriers: CSL Group and the Great Lakes Seaway

Nine Panamax bulk carriers in the CSL Great Lakes Seaway fleet were found non-compliant with Lloyd’s Register harmonic requirements during routine inspection. VFD-driven loads on each vessel were generating harmonic currents exceeding the limits. Mirus Lineator filters brought all nine vessels into compliance — documented with before/after measurements on representative vessels.

Erstaunlicher Intl – Harmonic Control at a Remote Oil Well: Better Than 18-Pulse Performance at 12-Pulse Cost

Remote oil well site with a single-drive VFD application: multi-pulse transformer approaches were impractical at this location. Mirus Lineator passive filter achieved better than 18-pulse harmonic performance at 12-pulse cost — measured THID below 5% at the drive input. The case demonstrates that passive harmonic filters can outperform multi-pulse transformers in single-drive, isolated applications.

Erstaunlicher Intl – Harmonic Mitigation for a Generator-Fed Motor Control Centre: Natural Gas Sweetening Plant

Natural gas sweetening plant with a generator-fed motor control centre: the generator’s high source impedance amplified harmonic voltage distortion from VFD loads to levels that caused control system malfunctions. Mirus filter selection had to account for the generator impedance characteristics rather than infinite bus assumptions — a common oversight in generator-fed harmonic filter design.

Erstaunlicher Intl – Marine Duty Harmonic Mitigation Saves an Offshore Service Vessel Program

An offshore service vessel DC drive system produced voltage notching severe enough to cause control system malfunctions on other vessel systems. The vessel program was at risk of cancellation. A Mirus Lineator filter on the DC drive eliminated the notching — restoring compatibility between the drive and the vessel’s sensitive electronics. Documented with oscilloscope waveforms before and after.

Erstaunlicher Intl – Harmonic Mitigation and Generator RightsizingA Pipeline Pumping Station Case Study

Pipeline pumping station with generator-fed VFDs: harmonic current from the drives caused the generator to be significantly oversized — adding capital cost and reducing fuel efficiency. Mirus sinewave filter reduced harmonic current to allow generator rightsizing, improving fuel efficiency and reducing the generator procurement cost. Field results show measured harmonic distortion and generator loading before and after.

Erstaunlicher Intl – Sinewave Filters for ESP Motor Protection: A Field Case Study in Filter Design and Motor Thermal Response

Submersible ESP (Electric Submersible Pump) motors fed via VFDs through long cables: sinewave filter design must account for the cable capacitance, motor inductance, and the filter’s own resonant frequency. Incorrect filter design can produce resonance at a harmonic frequency, amplifying distortion rather than reducing it. Case documents the filter design process and measured thermal response of the motor under harmonic loading.

Ein praktischer Fall von Power Quality Study (Olivenbaum, Jose C.)

IEEE conference paper by Prof. José Carlos de Oliveira (Federal University of Uberlândia) — site measurements at a Brazilian textile factory. Four-parameter framework: voltage profile, harmonische Verzerrungen, Spannungsunsymmetrie, and feeder transfer risk. A foundational industrial PQ assessment methodology paper. The PDF is available for download from the IPQDF library.

Bezeichnung des Ungesunde Power Systems mit nicht-Charateristic Harmonics

Non-characteristic harmonics — orders not predicted by the standard 6k±1 formula for 6-pulse rectifiers — appear in power systems with converter firing angle asymmetry, supply unbalance, or multiple overlapping non-linear loads. Schlumberger/IEEE paper presents an identification methodology using harmonic fingerprinting to detect unhealthy power systems from their non-characteristic harmonic signature.

Harmonics Case Study

A major food processing and distribution centre in Dortmund, Germany — 100,000 m² facility — experienced production disruptions and equipment malfunctions from harmonic distortion generated by VFDs in the highly automated facility. Active harmonic filter installation reduced current THD and eliminated the production disruptions. Before/after measurements confirm compliance with German grid code.

Harmonics Mitigation auf VFD

GRYAAB Gothenburg sewage works used variable-speed pumps to process wastewater — but VFD harmonic currents limited pump output to below the theoretical maximum. Active harmonic filter installation optimised VFD electrical behaviour, enabling 30% more throughput during peak demand periods. Energy savings were a secondary benefit — the primary gain was process capacity.

STATCOM Case Study

Europe’s largest steel wire producer faced a tightened flicker limit from the utility as local grid usage increased. Spot welders from Schlatter AG produced flicker emissions exceeding the new limit. A STATCOM installation reduced flicker to compliant levels — the case documents the assessment methodology, STATCOM sizing, and before/after measurement results.

Oberschwingungen und Kerben im dynamischen Test Load

A major European manufacturer’s dynamic test bench — with highly variable loading — produced harmonics up to and beyond the 100th order plus voltage notching that corrupted test results. Active harmonic filters compensating up to the 100th order eliminated both phenomena, restoring the integrity of development testing and preventing false test failures from power supply artefacts.

Aktive Oberschwingungsfilter in Druckanwendungen

Amsterdam printing company producing 1 million papers daily with presses running almost continuously experienced PQ problems manifesting as production downtime and fluorescent lighting interference. Active harmonic filter installation reduced current THD, stabilised voltage, eliminated the lighting flicker, and reduced measured downtime. Before/after voltage waveform comparison shows the improvement.

Harmonics-Generation, Vermehrung und Spülen Techniques in nichtlinearen Lasten

Saudi Arabia academic review of harmonic generation mechanisms, propagation paths, and mitigation techniques for non-linear loads — covering passive filters, active filters, hybrid approaches, and multi-pulse converters. Provides theoretical grounding for harmonic mitigation selection, with worked examples for different industrial load types. King Saud University publication.

Auch Harmonic Resonance- ein Problem Unsual

Chemical plant using large static converters for electrochemical processes experienced repeated harmonic filter failures. Investigation revealed even harmonic resonance — an unusual problem typically found only in uncontrolled rectifiers or systems with DC offset. The even harmonics were caused by asymmetrical firing of the converter’s thyristors, creating 2nd and 4th harmonic currents that the filter was not designed to handle.

Harmonic Filter Design Zwei Resonant Punkte in einer Distribution Network Mitigate

South African distribution network with two resonant points at different harmonic orders — a single-tuned filter addresses one resonance but can amplify the other. Case from Cape Peninsula University of Technology documents the filter design process for a network with two resonant frequencies, requiring a carefully detuned double-tuned filter to address both simultaneously.

Capacitor Failure Analysis (Eaton)

A steel processing plant experienced unexplained capacitor failures and fuse operations in an automatically switched capacitor bank. Eaton Engineering investigation revealed harmonic resonance between the capacitor bank and system impedance — at a specific harmonic order, the impedance was amplified, overloading the capacitors well beyond their rated capability. Classic harmonic-capacitor resonance case with full analytical solution.

Stromrichter und Power Quality

Laboratory measurements on a 2.2 kW adjustable speed drive subjected to controlled voltage dips of varying magnitude and duration. The ASD’s DC bus capacitors and ride-through capability are characterised — showing the boundary between ride-through and trip as a function of sag depth and duration. Provides the experimental basis for ASD immunity specification in sensitive industrial applications.

Steel Factory Erdungssystem

A steel factory in northern Italy had all laboratory electronic equipment behaving erratically — seemingly without cause. Investigation revealed constructive defects in the earthing system creating large current loops. With heavy currents flowing through the earth return path, the potential difference between equipment earths was sufficient to cause data corruption and equipment malfunction throughout the plant.

Verteilte Stromerzeugung und Power Quality

Belgian MV distribution network segment used to study the impact of distributed generation technologies (wind, PV, CHP) on power quality and voltage stability. Four cable feeders from a 14 MVA 70/10 kV transformer. Analysis shows how DG penetration affects voltage profiles, harmonic injection, and voltage stability — with practical implications for network planning with high DG penetration.

Spannungs-und Stromoberschwingungen (John Wiley & Sons)

Six-pulse converter transformer selection and rating when harmonic spectrum is known. John Wiley Handbook of Power Quality chapter covers K-factor calculation, additional loss estimation, and de-rating methodology for transformers feeding rectifier loads. Provides the calculation procedure engineers need to correctly specify transformers for non-linear load environments.

ADF Verbessert dynamischen Prüfstand (Comsys AB)

Dynamic test bench with programmable loading patterns produced harmonics up to the 100th order and significant voltage notching. Comsys ADF Active Harmonic Filter installation reduced notching and harmonic distortion, restoring supply quality to other equipment on the same transformer. A duplicate of case 2328 with slightly different background — Comsys vs. Active Harmonic Filters branding.

ADF Sichere Nahrungsmittelproduktion Schadensbegrenzende Harmonics (Comsys AB)

REWE Dortmund distribution centre — rebuilt and expanded butcher facility with high VFD density — experienced harmonics causing machinery malfunctions. Comsys ADF active harmonic filter brought current THD within acceptable limits and eliminated the machinery problems. Duplicate of case 2336 with Comsys branding — same REWE Dortmund facility, same solution.

ADF Erhöht Water Treatment Plant Output von 30% (Comsys AB)

GRYAAB Ryaverket sewage works in Gothenburg — one of Scandinavia’s largest treatment plants — used VFD-controlled pumps. Comsys ADF active harmonic filter optimised VFD electrical behaviour, allowing 30% more fluid processing capacity during peak periods with simultaneous energy savings. Duplicate of case 2334 with Comsys branding — same Gothenburg facility.

Harmonischen hoher Ordnung (HIOKI)

Power supplies with semiconductor control devices generate high-frequency noise above several kHz — high-order harmonics that cause equipment malfunction and radio/TV interference. HIOKI measurement at 1-phase 100V shows the frequency spectrum, resonance amplification effects, and the threshold at which the noise becomes dangerous to connected equipment.

Zufluss und Abfluss von Oberschwingungen (HIOKI)

HIOKI technical guide to determining whether harmonics are flowing from a facility into the grid or from the grid into the facility — the fundamental question for harmonic source attribution. Covers power direction measurement methods, Japanese utility guideline compliance assessment, and field measurement examples showing both inflow and outflow scenarios with the HIOKI PW3198.

Fehlerhafte medizinisches Gerät (Fluke)

A building manager with widespread electrical malfunctions and three electricians who quit — none could identify the problem. A systematic approach starting with current measurement revealed a tripped GFCI with high neutral current feeding a malfunctioning medical device. Classic case demonstrating that systematic PQ investigation beats component replacement as a troubleshooting strategy.

Rural Transformator Ausfall (Fluke)

Rural transformer failure at the end of a medium-voltage feeder serving an apartment complex, dairy farm, and golf course. Fluke investigation found the transformer failed from sustained overloading combined with harmonic current from a variable-speed pump at the dairy farm. Demonstrates that harmonics contribute to transformer failure through additional winding losses — even in rural settings withcleanloads.

Fehlerhafte Ampel (Fluke)

Traffic light controller at a main town intersection malfunctioning randomly — sometimes working, sometimes causing long unexplained delays in one direction. Fluke 43B investigation found voltage unbalance and harmonics from a nearby industrial customer on the same distribution transformer. The traffic light controller was sensitive to supply quality — a finding not obvious without measurement.

Mechanische Werkstatt Motorausfälle (Fluke)

Machine shop motors failing repeatedly despite no change in mechanical loads and other equipment on the same service working normally. Motor rewind shop supervisor used Fluke measurement to identify voltage unbalance plus harmonic distortion — classic combination that produces negative-sequence rotor currents, dramatically increasing motor winding temperature and shortening motor life.

Lighting Vorschaltgerät Auswertung (Fluke)

Lighting maintenance in large facilities is a major cost — especially with high ceilings requiring personnel lifts. This Fluke case study evaluates whether replacing existing ballasts with electronic ballasts reduces maintenance costs enough to justify the capital investment, using measured power factor, harmonic content, and lamp life data to build the economic case.

Halbwellengleichrichter (Fluke)

A school district transformer making achatteringnoise with heavily loaded secondary — loads including lights, elektrische Heizung, and computers. A half-wave rectifier in a fan motor heater combination was generating DC current and even harmonics, causing the transformer core to saturate asymmetrically and vibrate audibly. Classic even harmonic / DC injection problem from a defective single-phase load.

Wind Generation Power Quality & Interconnect Fragen (Dranetz)

Wind generation plant interconnection requires assessment of harmonics, Flimmern, voltage fluctuation, frequency deviation, and fault ride-through capability. Dranetz monitoring solutions cover both temporary commissioning assessment and permanent 24/7 monitoring for continuous interconnection compliance verification on wind farms of any size.

Glass Factory Ausfall Electronic Controls Case Study (Dranetz)

A glass factory imported from a 60 Hz country to a 50 Hz country suffered repeated electronic control failures, reducing production capacity by 50%. Voltmeters and simple monitors failed to capture the cause. Full PQ monitoring eventually revealed voltage transients and harmonic distortion incompatible with the 60 Hz-designed electronics — a frequency migration problem compounded by poor power quality.

Flüssig-und Gas-Pumpe / Pipeline Anwendungen (American Superconductor)

Pipeline pump stations are moving to larger motors — 4160V in the 2,000–4,000 HP range, 15kV-class at 8,000–15,000 HP — creating significant flicker, Harmonische, and reactive power management challenges. American Superconductor’s PQ-SVC system provides dynamic reactive compensation enabling larger motor sizes at existing substations without requiring substation upgrades.

Harmonic Probleme in einem Casino

Michigan casino with 1000 slot machines planned 500 more — but the utility measured 5% THDv at the PCC and demanded correction before allowing the expansion. Interference on CCTV security monitors was also traced to harmonic distortion. Arteche zigzag transformer eliminated third-harmonic triplen currents, allowing the casino expansion to proceed within the utility’s voltage distortion limit.