التشوه فوق التوافقي في شبكات الجهد المتوسط والمنخفض - أربعة تأثيرات سلبية موثقة وفجوة الحدود
Four documented negative effects of supraharmonic distortion (2-150 كيلو هرتز) on MV and LV distribution networks: power loss and heating from skin effect, dielectric material aging at accelerated stress cycle rates, MV cable termination failures from combined dielectric stress and local heating, and PLC interference in smart metering and demand response systems. النتيجة الرئيسية: MV/LV transformer transfer ratio is 0.5–3.0 — some supraharmonic components are amplified crossing from MV to LV. Strong correlation measured at substations 16 كم على حدة. No planning or compatibility limits currently exist above 9 كيلوهرتز.