Zig-Zag Reactors for Zero-Sequence Current Supply for Weak Power Systems

Zig-Zag Reactors for Zero-Sequence Current Supply for Weak Power Systems – IPQDF
Denis Ruest, IPQDF  ·  Technical Reference Series
Ground Fault Protection Zig-Zag Reactor Renewable Energy IEC 60076-6 · IEC 61869-2

Modern electrical distribution networks — particularly long radial three-phase feeders supplying remote loads, rural infrastructure, or renewable energy collection systems — present a fundamental protection challenge that is often underestimated at the system design stage. As the penetration of inverter-based generation (photovoltaic, wind, battery storage) increases, the short-circuit behaviour of these networks departs significantly from the assumptions embedded in conventional overcurrent and earth fault protection philosophies.

A central statistic motivates the discussion: single-phase-to-ground faults are by far the most frequent fault type in power systems, accounting for approximately 70–80% of all recorded fault events [1,2,3]. This figure is consistent across medium-voltage (MV, 1–36 kV) and high-voltage (HV, 36–150 kV) distribution networks worldwide and has been confirmed in multiple peer-reviewed studies of 6–66 kV systems. The dominance of single-phase ground faults arises from the physical vulnerability of individual phase conductors to insulation degradation, wildlife contact, vegetation encroachment, conductor galloping, and mechanical damage — all statistically far more likely to affect one phase at a time than to produce a simultaneous multi-phase event [4].

On a long distribution feeder, this is compounded by impedance. Source impedance increases with line length, reducing available fault current at the remote end. On an inverter-dominated network, grid-following inverters typically limit their output current to 1.0–1.2 times rated current within a few milliseconds of fault inception [5]. The result: a single-phase ground fault at the far end of a long feeder may produce a fault current indistinguishable from a normal load unbalance. The earth fault relay sees no credible pickup signal, the fault persists, and the probability of escalation to a multi-phase event increases significantly.

This problem is not new to renewable energy sites. Remote communities, mining camps, offshore platforms, and rural areas supplied by diesel generators have faced the same challenge for decades. A diesel generator’s subtransient reactance X″d (the reactance governing fault current in the first few cycles), transient reactance X′d (governing the following seconds), and synchronous reactance Xd (the steady-state value) typically produce a three-phase fault current of only 5–10 times rated — already modest compared to a strong grid connection. For a single-phase-to-ground fault, which must drive current through the series combination of positive-, negative-, and zero-sequence impedances, the fault current is lower still. If the generator neutral is left unearthed or earthed through high impedance to limit stator winding damage — which is common practice — the zero-sequence impedance seen from the fault can be very large, producing a ground fault current that falls below the pickup of any conventional overcurrent relay. Remote area power supply (RAPS) engineers have managed this limitation for years, typically through careful neutral earthing schemes and sensitive voltage-based detection. The zig-zag reactor addresses it more directly and more completely, as this article describes.

The solution in both contexts is the deliberate introduction of a low zero-sequence impedance path at an appropriate point in the network — a piece of equipment that provides a stable, well-characterised ground reference and a controlled fault current magnitude, independently of the generation technology connected. Two equipment topologies accomplish this: the star-delta transformer (familiar from conventional power system practice) and the purpose-built zig-zag reactor. This article covers the operating principles of both, compares their zero-sequence impedance characteristics, and provides a complete specification methodology for the zig-zag reactor — including tap selection, capacity rating, and protection coordination.

Scope
Equations are parametric — no specific voltage level is assumed in the theory sections. A fully worked numerical example using a 13.8 kV / 5 MVA islanded renewable energy site is developed in Section 4, with a downloadable calculation sheet provided for adaptation to other voltage levels. The zig-zag reactor is treated as primary electrical equipment with its own equipment tag, asset register entry, and maintenance schedule.

1. The Zig-Zag Winding — Operating Principle

1.1 Winding configuration

A zig-zag winding (also termed an interconnected-star winding) subdivides each phase into two half-windings distributed across two separate limbs of a three-leg core. On each limb, one half-winding belongs to one phase and the second belongs to a different phase, connected in series with reversed polarity. The six half-windings are interconnected so that their junction points form the line terminals and their common point forms the neutral.

As a purpose-built reactor — rather than a power transformer — the unit is wound on an air-gapped three-leg core. The air gap on each limb linearises the magnetic characteristic of the core, preventing saturation under sustained fault current and making the zero-sequence impedance Z₀ predictable and stable across the full current range from no-load to maximum fault current. The gap width is the primary means by which the manufacturer sets Z₀ to the specified value.

The air gap is essential not only for controlling Z₀ but also for eliminating the nonlinear inductance that would otherwise make the reactor susceptible to ferroresonance on capacitive cable networks. An ungapped transformer used as an interim grounding unit does not have this protection — ferroresonance has been observed in practice on cable-fed 12–35 kV substations using ungapped grounding transformers. With the air-gapped core, the linear inductance cannot sustain ferroresonance regardless of the network capacitance.

gap gap gap A1 C2 B1 A2 C1 B2 Terminal A Terminal B Terminal C N (neutral) Phase A windings Phase B windings Phase C windings Zig interconnection Air gap (essential) Core (3-leg)
Fig. 1 — Air-gapped three-leg core zig-zag reactor. Each limb carries one upper and one lower half-winding from two different phases in series with opposing polarity. The air gap on each limb (dashed white break) linearises the magnetic characteristic, sets Z₀ to the specified value, and eliminates ferroresonance susceptibility on capacitive cable networks.

1.2 Magnetomotive force cancellation and zero-sequence conduction

For positive- or negative-sequence currents, the two half-windings on each limb carry currents 120° apart — their magnetomotive forces (MMFs) partially cancel and the reactor presents high leakage impedance to the network. For zero-sequence currents (all three phases in phase), the MMFs on each limb add, the reactor conducts freely, and the sum 3I₀ returns via the neutral terminal.

Positive-sequence (load) Ia Ib Ic Z trap I_N = 0 High Z — MMFs cancel Zero-sequence (fault) I₀ I₀ I₀ Z trap 3I₀ → neutral / ground Low Z — MMFs add
Fig. 2 — Balanced positive-sequence load (left) vs zero-sequence ground fault (right). Under balanced conditions I_N = 0 — the reactor is transparent. During a fault all three phases carry in-phase I₀; these sum to 3I₀ at the neutral terminal.

1.3 Sequence impedance summary

SequenceImpedance seen by networkPhysical mechanism
Positive (Z₁)High — leakage reactance onlyMMFs partially cancel; no circulating path
Negative (Z₂)High — approximately equal to Z₁Same MMF cancellation as positive sequence
Zero (Z₀)Low — set by air gap designMMFs add; reactor conducts freely; neutral provides return

2. Comparison with the Star-Delta Transformer

2.1 Network equivalence

An unloaded star-delta transformer — whose delta secondary winding is closed on itself but feeds no external load — is electrically equivalent to a zig-zag reactor from the perspective of the upstream network. Both present high positive- and negative-sequence impedances and a low zero-sequence impedance shunted to the neutral. Both circulate zero-sequence and triplen harmonic currents internally.

Zig-zag reactor A B C N (no secondary output) Star-delta, no load A B C Y N Δ closed (delta unloaded, open terminals) network view Sequence network equivalent (identical for both) Positive-sequence Z₁ ≈ open (high) no contribution Negative-sequence Z₂ ≈ open (high) no contribution Zero-sequence Z₀ = low shunt to ref (ground)
Fig. 3 — Network equivalence between the zig-zag reactor and an unloaded star-delta transformer. Both present the same sequence network: high Z₁ and Z₂, low Z₀ shunted to the reference bus.

2.2 Cost — the primary advantage of the zig-zag

A zig-zag reactor uses only one set of windings per phase. A star-delta unit achieving the same zero-sequence impedance needs two full winding sets. For a device whose sole function is zero-sequence current supply, the extra material represents waste. The zig-zag delivers the same zero-sequence shunt at roughly half the active material, typically translating to 40–60% lower cost at equivalent kilovolt-ampere (kVA) rating and voltage class.

2.3 Limitations of the star-delta approach

AspectStar-delta (no load)Purpose-built zig-zag reactor
Zero-sequence Z₀Fixed at manufacture; may not suit protectionSpecified to target fault current
Ferroresonance riskYes — ungapped core on capacitive networksNo — air gap linearises inductance
Material and costTwo full winding sets — higher costOne winding set — 40–60% lower cost
Triplen harmonic filteringYes — circulates in delta windingYes — circulates in zig-zag winding
Tap adjustmentNot available after manufactureCan be specified with taps

3. Zero-Sequence Impedance and the Sequence Network

3.1 The sequence network for a single-phase-to-ground fault

For a solid phase-to-ground fault the three sequence networks are connected in series. The zig-zag reactor appears only in the zero-sequence network — it contributes nothing to Z₁ or Z₂. On a weak inverter-based or diesel-fed system where Z₁ is large, reducing Z₀ via the reactor has a proportionally larger effect on fault current than the same change would produce in a stiff grid-connected network.

Positive-sequence Negative-sequence Zero-sequence Z₁ (source) Z_sys V source Unchanged by Z trap Z₂ (source) Z_sys Unchanged by Z trap Zero-sequence Z₀_sys Z_sys Z₀_zig Z_trap Z trap reduces Z₀_total series series I_f = 3V_ph / (Z₁ + Z₂ + Z₀_total) Z₀_total = Z₀_sys ∥ Z₀_zig — Z trap lowers this, raising I_f In a weak system: Z₁ and Z₂ are large — reducing Z₀ via the Z trap has proportionally more impact on I_f than in a stiff network
Fig. 4 — Sequence network for a single-phase-to-ground fault. The zig-zag reactor appears only in the zero-sequence network as a shunt Z₀ to the reference bus. On a weak system with large Z₁ and Z₂, lowering Z₀ has proportionally more impact on I_f.

3.2 Zero-sequence impedance — zig-zag reactor

Eq. 1
\( Z_0 = \dfrac{V^2_{LL}}{S_0} \)
Z₀ in Ω; V_LL = line-to-line voltage (V); S₀ = rated zero-sequence kVA

In per unit (pu) on the system base:

Eq. 2
\( z_0\,(\text{pu}) = \dfrac{S_\text{base}}{S_0} \times z_{0,\text{rated}} \)
z₀_rated as a fraction from the reactor nameplate

3.3 Zero-sequence impedance — star-delta transformer

Eq. 3
\( Z_0 = z_k \times \dfrac{V^2_{LL}}{S_\text{rated}} \)
z_k = per-unit leakage impedance from nameplate; typically 0.04–0.08 pu; fixed at manufacture
Contribution to short-circuit power
The zig-zag reactor does not contribute to three-phase short-circuit megavolt-ampere (MVA). However, it materially increases the single-phase-to-ground fault current by lowering Z₀_total. This effect must be accounted for in protection coordination and equipment ratings.

4. Specifying the Zig-Zag Reactor

4.1 Design objective

The specification starts from two boundary conditions that bracket the acceptable zero-sequence impedance:

  • Minimum fault current If,min — the lowest single-phase-to-ground fault current that guarantees reliable earth fault relay operation, accounting for arc resistance and remote fault location. A sensitivity margin of 1.5–2.0 is recommended: If,min ≥ 2 × Ipickup.
  • Maximum fault current If,max — the highest fault current the system can sustain without exceeding the ratings of cables, switchgear, the neutral current transformer (CT), and the reactor short-time rating.

4.2 Arc resistance and the Warrington formula

Single-phase ground faults on overhead lines and open switchgear typically involve an electric arc rather than a solid metallic contact. Arc resistance is not constant — it depends on arc current and arc length. The empirical Warrington formula gives a practical estimate:

Eq. 4
\( R_\text{arc} = \dfrac{28{,}730 \times L}{I_f^{1.4}} \)
L = arc length in metres; I_f = fault current in amperes; R_arc in ohms
Arc resistance — design basis
For a 0.3 m arc at 337 A, the Warrington formula gives R_arc ≈ 7–10 Ω. The worked example in this article uses Z_f = 20 Ω — a conservative value implying a longer arc (≈ 0.6–0.8 m) or a deliberate safety margin. This is the correct design basis: specify for the worst-case arc resistance, and the relay will also operate for shorter, lower-impedance arcs. See the arc resistance sensitivity table in the worked example below.

4.3 Key equations

Eq. 5
\( I_f = \dfrac{3\,V_\text{ph}}{Z_1 + Z_2 + Z_{0,\text{total}} + 3Z_f} \)
V_ph = V_LL / √3; Z_f = arc resistance; all impedances in Ω
Eq. 6
\( Z_{0,\text{design}} = \dfrac{3\,V_\text{ph}}{I_{f,\text{target}}} – Z_1 – Z_2 – 3Z_f \)
Target Z₀ from desired fault current — includes arc resistance term
Eq. 7
\( S_0 = 3 \times \dfrac{V_n}{\sqrt{3}} \times I_{f,\text{max}} \)
Reactor kVA rating — short-time duty at maximum fault current
Eq. 8
\( I^2_{f,\text{max}} \times t_c \leq I^2t_\text{rated} \)
Short-time withstand — use backup protection clearing time as worst case

4.4 Worked example — 13.8 kV / 5 MVA islanded renewable energy site

System parameters
Voltage: 13.8 kV (line-to-line) · V_ph = 7,967 V  |  Rating: 5 MVA islanded site · I_rated = 209 A  |  Source: inverter-based, SCR = 5 · Z1_src = 1.0 + j7.6 Ω (delta-wye transformer blocks zero-sequence back-propagation)  |  Feeder: 5 km overhead, 70 mm² ACSR · Z1_line = 2.2 + j1.7 Ω · Z0_line = 8.0 + j5.0 Ω  |  Reactor: Z0_reactor = j4.5 Ω (air-gapped three-leg core)  |  Arc fault: Z_f = 20 Ω (conservative basis)

Step 1 — Total positive-sequence impedance:

Z1_total
\( = (1.0+j7.6) + (2.2+j1.7) = 3.2+j9.3\ \Omega \quad |Z_1| = 9.84\ \Omega \)
Z1 = Z2 (symmetrical)

Step 2 — Z0 parallel combination (reactor ∥ line):

Z0_total
\( = j4.5 \,\|\, (8+j5) = \dfrac{j4.5\,(8+j5)}{8+j9.5} = 1.05+j3.25\ \Omega \quad |Z_0| = 3.41\ \Omega \)
Parallel combination — full derivation in calc. sheet

Step 3 — Fault current without reactor:

No reactor
\( I_f = \dfrac{3 \times 7{,}967}{566.7} \approx 42\ \text{A} \quad (20\%\ \text{of rated}) \)
Z0 ≈ 500 Ω (capacitive path only) — undetectable

Step 4 — Fault current with reactor:

With reactor
\( I_f = \dfrac{3 \times 7{,}967}{70.9} = 337\ \text{A} \quad (161\%\ \text{of rated}) \quad \theta_f = 18°\ \text{lag} \)
Relay at 100 A pickup: margin = 3.4× · I₁ = I₂ = I₀ = 112 A
Result
The reactor raises fault current from 42 A (undetectable — 20% of rated) to 337 A (161% of rated) with a sensitivity margin of 3.4× at a 100 A relay pickup. The fault angle of 18° lag confirms that arc resistance dominates the impedance — this is the physical signature of a high-impedance arc fault.

4.5 Voltage at each measurement point

The positive-sequence current I₁ = 112 A flows through the feeder producing a voltage drop at every point. Va is never 100% anywhere on the network during a fault — the depression propagates to all points including downstream of the reactor. The difference between upstream fault (F1) and downstream fault (F2) is small at Points B and C — current magnitude and direction are the reliable discriminators, not voltage.

PointDescriptionVa — F1 upstreamVa — F2 downstream3V₀ — F13V₀ — F2Ia — F1Ia — F2
ASource bus94.3%89.2%~2.5% small≈ 0≈ 32 A112 A
BReactor bus87.5%86.1%1,517 V (19%)1,517 V (19%)150 A150 A
CLoad feeder87.5%86.1%01,149 V (14%)≈ 100 A load337 A
FFault point84.6%84.6%337 A · Va ∥ Ia (θ=0°)
Key insight — Point B neutral CT
The neutral CT at Point B reads |3I₀| = 337 A for both fault locations — identical magnitude. Va is only 1.4% different between F1 and F2 — indistinguishable in practice. The only reliable discriminator at Point B is the direction of 3I₀ relative to 3V₀, which requires phase CTs and a VT simultaneously — not a neutral CT alone. A 59N relay at Point A detects upstream faults by 3V₀ magnitude (present for F1, ≈0 for F2). A feeder overcurrent relay at Point C detects downstream faults by Ia magnitude (337 A for F2, load-only for F1).

4.6 Network topology and phasor diagrams

The following connection diagram shows the 13.8 kV / 5 MVA islanded site with the three measurement points and both fault locations. The phasor grid below shows what each measurement point sees — voltages and currents — for both fault cases, including Point F (the fault point itself).

Weak source (G) 5 MVA · 13.8 kV SCR=5 Z1=1+j7.6Ω Point A VT VT 5 km feeder · 70 mm² ACSR Z1=2.2+j1.7Ω Z0=8.0+j5.0Ω Upstream fault (F1) Point B VT+CTs VT Z-trap Z0 = j4.5 Ω N-CT Load feeder Point C CTs CTs Downstream fault (F2) Zf = 20 Ω arc Load consumers Without reactor: I_f = 42 A (20% rated) — undetectable With reactor: I_f = 337 A (161% rated) — relay operates · fault angle θ = 18° lag · Va at fault = 84.6%
Fig. 5 — Network topology for the 13.8 kV / 5 MVA islanded site. Point A (source bus) measures 3V₀ by VT — reliable discriminator for upstream faults. Point B (reactor bus) measures 3I₀ by neutral CT and phase currents by CTs plus VT — direction is the discriminator. Point C (load feeder) measures Ia — magnitude is the discriminator for downstream faults. F1 and F2 show the two fault locations; Zf = 20 Ω in both cases.
Upstream fault (F1) between source and reactor Downstream fault (F2) beyond reactor, toward load Point A Source bus F1: Va=94.3% F2: Va=89.2% 3V₀: 2% / ≈0 Point B Reactor bus Va: 87.5%/86.1% 3V₀=1,517V both 3I₀=337A N-CT dir. differs only Point C Load feeder Va: 87.5%/86.1% F1: Ia=load only F2: Ia=337A 3V₀=0/1,149V Point F Fault point Va=84.6% both Ia=337A both Va ∥ Ia θ=0° pure resistive arc Legend Va Vb Vc Ia faulted Ib Ic healthy 3V₀ 3I₀ neutral CT Outer circle=100% V: 80px=Vph_nom I: 15px per 100A 13.8 kV / 5 MVA · 5 km feeder · Zf=20Ω arc · Z0_reactor=j4.5Ω · I_f=337A · I₁=I₂=I₀=112A · θ=18° lag Va 94.3% Vb 106% Vc 106% 3V₀ small Ia≈32A 3V₀ small — upstream fault weakly visible at A Va 89.2% Vb 104% Vc 104% 3V₀≈0 Ia=112A Ia=Ib=Ic=I₁=112A 3V₀≈0 — reactor shields source from downstream fault Va 87.5% Vb 105% Vc 105% 3V₀=1,517V 3I₀→src Ia≈150A Ib≈90A Ic≈130A N-CT: 3I₀=337A — toward source Va 86.1% Vb 105% Vc 105% 3V₀=1,517V 3I₀→load Ia≈150A Ib≈130A Ic≈90A N-CT: same 3I₀=337A — direction reversed Point B: |3I₀| identical both cases (Va differs only 1.4%) — 3I₀ direction is the only discriminator Phase CTs + VT needed to resolve direction. Neutral CT alone cannot discriminate upstream vs downstream. Va 87.5% Vb 105% Vc 105% 3V₀ = 0 Ia Ib Ic balanced — load only ≈100A Unaffected — no fault current flows through C Va 86.1% Vb 105% Vc 105% 3V₀=1,149V Ia=337A Ib=112A Ic=112A Ia=337A dominant — feeder relay operates Point F is the fault point itself — phasors are identical for F1 and F2 (same I_f, same arc voltage, same angle) Va 84.6% Vb 107% Vc 107% 3V₀=1,149V Ia=337A θ=0° Va ∥ Ia Ib=112A Ic=112A Va and Ia in phase (θ=0°) Arc fault is purely resistive — Zf=20Ω Va 84.6% Vb 107% Vc 107% 3V₀=1,149V Ia=337A θ=0° Va ∥ Ia Ib=112A Ic=112A Va and Ia in phase (θ=0°) Ib=Ic=I₀=112A — all phases carry zero-seq current
Fig. 6 — Complete 2×4 phasor grid for the 13.8 kV / 5 MVA worked example (Zf = 20 Ω arc, Z0_reactor = j4.5 Ω, I_f = 337 A). Rows: Point A (source bus) · Point B (reactor bus) · Point C (load feeder) · Point F (fault point). Columns: upstream fault F1 · downstream fault F2. The outer dashed circle represents 100% of Vph_nom (7,967 V); voltage phasors are drawn to scale. Current scale: 15 px per 100 A. The Point F row shows Va and Ia exactly in phase (θ = 0°) — the physical signature of a purely resistive arc fault.

4.7 Arc resistance sensitivity

The following table shows how fault current varies with arc resistance for this system. The calculation is iterative for the Warrington cases — R_arc depends on I_f which depends on R_arc. Design is always based on the highest arc resistance (lowest fault current) — if the relay operates at 337 A it will certainly operate at 624 A or 815 A.

Z_f (Ω)ScenarioI_f (A)% ratedMargin at 100 A pickup
0Bolted fault815390%×8.2
5Warrington — 0.3 m arc (converged)624299%×6.2
10Warrington — 0.5 m arc approx.472226%×4.7
20Design basis — conservative337161%×3.4 ← governs specification
40Long arc / resistive ground216103%×2.2

4.8 Downloadable calculation sheet

A complete step-by-step calculation sheet covering all equations, the full voltage table, the arc resistance sensitivity analysis, and an adaptation template for other voltage levels is available for download:

Download calculation sheet (.docx)

5. Tap Selection and Adjustment Over Time

5.1 Rationale

Renewable energy and remote power sites are not static: generation capacity is added in phases, grid connection impedances change as the upstream network reinforces, and protection settings are refined with operational experience. Each change alters Z₁ and Z₂ and shifts the ground fault current that a fixed-Z₀ reactor produces. Specifying taps at the outset provides field-adjustable Z₀ without equipment replacement.

Tap changes must be made off-load and de-energised using an off-circuit tap changer. On-load tap changing is not appropriate for grounding reactors whose operating duty is intermittent rather than continuous.

5.2 Fault current and reactor loading at each tap

Eq. 9
\( I_f(\text{tap}) = \dfrac{3V_\text{ph}}{Z_1 + Z_2 + Z_0(\text{tap}) + 3Z_f} \)
Z₀(tap) varies with tap position; Z_f = arc resistance
Eq. 10
\( S(\text{tap}) = 3 \times V_\text{ph}(\text{tap}) \times I_f(\text{tap}) \)
Verify against rated kVA at every tap position
Eq. 11
\( I^2_f(\text{tap}) \times t_c \leq I^2t_\text{rated} \)
Must be satisfied at every tap position — most onerous governs

5.3 Representative tap schedule

TapZ₀ (rel. to nominal)I_fS(tap)I²t check
1 (max Z₀)1.20 × Z₀,nomI_f,minS_min≥ I²t_rated
21.10 × Z₀,nomI_f,2S_2≥ I²t_rated
3 (nominal)Z₀,nomI_f,nomS_nom≥ I²t_rated
40.90 × Z₀,nomI_f,4S_4≥ I²t_rated
5 (min Z₀)0.80 × Z₀,nomI_f,maxS_maxMost onerous — governs rating

6. Protection — Neutral CT, Relay Coordination, and Thermal Rating

6.1 Neutral current transformer

A current transformer (CT) installed on the neutral-to-ground connection of the zig-zag reactor measures the zero-sequence fault current 3I₀ during a ground fault and carries negligible current under balanced conditions.

ParameterRequirementStandard
Primary ratingI_CT ≥ I_f,max at lowest tap (Eq. 9 at tap 5)IEC 61869-2
Accuracy classClass 5P or 10P for protectionIEC 61869-2
Accuracy limit factor (ALF)I_CT × ALF ≥ I_f,max — CT must not saturate during maximum fault currentIEC 61869-2
Dynamic ratingI_peak = k√2 × I_f,max where k = DC offset factor (1.5–2.5 depending on X/R ratio of Z₀)IEC 61869-2
BurdenCT burden ≤ rated burden at specified accuracy classIEC 61869-2

6.2 Earth fault relay coordination

The earth fault relay on the neutral CT operates as a definite-time or inverse definite minimum time (IDMT) overcurrent element. Its pickup current Ipickup and time multiplier setting (TMS) must satisfy:

  • Sensitivity: Ipickup ≤ If,min / 2 — sensitivity margin of 1.5–2.0 recommended.
  • Selectivity: Grade with downstream feeder earth fault relays — grading margin ≥ 0.3–0.4 s for definite-time.
  • Stability under load unbalance: Long feeders with single-phase loads may produce a standing 3I₀ component. Set Ipickup above worst-case load unbalance.

6.3 Thermal rating and short-time duty

Eq. 12
\( I^2_{f,\text{max}} \times t_{c,\text{backup}} \leq I^2t_\text{rated} \)
Use backup protection clearing time — the governing worst case per IEC 60076-6

6.4 Protection checklist

ItemParameter to specifyGoverning reference
Neutral CT primary ratingI_CT ≥ I_f,max at lowest tapEq. 9 at tap 5
CT accuracy class5P or 10PIEC 61869-2
CT accuracy limit factorI_CT × ALF ≥ I_f,maxIEC 61869-2
CT dynamic ratingI_peak = k√2 × I_f,maxIEC 61869-2
Relay pickupI_pickup ≤ I_f,min / 2Sensitivity margin 1.5–2.0
Relay gradingt_grading ≥ 0.3 s above downstream feeder relayProtection coordination study
Reactor I²t withstandI²_f,max × t_c,backup ≤ I²t_ratedIEC 60076-6; Eq. 12
Tap-by-tap I²t checkEq. 9–11 at all tap positionsMost onerous tap governs

7. Alternative Approach — Voltage-Based Detection Without a Reactor

Installing a zig-zag reactor creates zero-sequence fault current by design. Before the reactor exists — or on a system where the reactor has not yet been specified — there is essentially no zero-sequence current to measure on a weak network. Under these conditions, conventional overcurrent-based earth fault protection cannot operate reliably.

If a reactor is not installed, the only viable detection method is voltage-based. A single-phase-to-ground fault on an unearthed or high-impedance earthed network causes a voltage unbalance that is measurable even when the fault current is negligible. Two instrument transformer arrangements provide this signal:

The first uses a voltage transformer (VT) connected in open-delta (also called broken-delta) on the secondary, with the primary windings connected star to earth. The open-delta secondary voltage is the zero-sequence voltage 3V₀. Under balanced conditions 3V₀ is zero. During a single-phase fault it rises — on a solidly unearthed system it can approach the full phase-to-phase voltage. A voltage relay monitoring the open-delta output can initiate an alarm or a timed trip.

The second arrangement uses a star-connected VT with the neutral brought out, allowing 3V₀ to be measured directly as the neutral point displacement from earth potential.

Both arrangements detect that a fault exists somewhere on the network. They do not identify which feeder is faulted and they provide no directional information. Tripping on voltage displacement alone disconnects the entire busbar.

Reactor vs voltage-based detection — the key distinction
The voltage-based approach is a passive detection scheme — it observes a consequence of the fault (voltage unbalance) but cannot influence the fault current. The zig-zag reactor is an active zero-sequence current source — it creates the fault current that makes overcurrent protection viable, enables feeder-level selectivity, and gives circuit breakers something meaningful to interrupt. As demonstrated in the worked example (Section 4), the reactor raises fault current from 42 A (undetectable) to 337 A with a 3.4× relay margin, while the voltage depression at Point A provides complementary discrimination between upstream and downstream faults via 3V₀ measurement.

In practice, the most robust protection scheme for a weak remote system combines both: the zig-zag reactor to establish a defined zero-sequence current source, and a 3V₀ measurement at the source bus (Point A) to provide the reference signal for the directional earth fault element (ANSI 67N). The phasor grid in Fig. 6 illustrates the complete picture — 3V₀ at Point A is ~2.5% for an upstream fault and ≈0 for a downstream fault, providing the upstream/downstream discrimination that the neutral CT at Point B cannot resolve alone.

References

  1. Wu, Z. et al., “Single-phase grounding fault types identification based on multi-feature transformation and fusion,” Sensors, vol. 22, no. 9, p. 3521, 2022. https://doi.org/10.3390/s22093521
  2. Liu, J. et al., “The classification model for identifying single-phase earth ground faults in the distribution network jointly driven by physical model and machine learning,” Frontiers in Energy Research, 2022. https://doi.org/10.3389/fenrg.2022.919041
  3. Song, G. et al., “Faulty feeder detection for single-phase-to-ground fault in resonant grounding system based on transition resistance estimation,” Electric Power Systems Research, 2025. https://doi.org/10.1016/j.epsr.2025.110655
  4. Elprocus, “Types of faults in electrical power systems and their effects,” 2021. Available: https://www.elprocus.com/what-are-the-different-types-of-faults-in-electrical-power-systems/
  5. Teodorescu, R., Liserre, M., and Rodríguez, P., Grid Converters for Photovoltaic and Wind Power Systems. Chichester: Wiley-IEEE Press, 2011.
  6. IEC 60076-6:2007, Power Transformers — Part 6: Reactors. Geneva: International Electrotechnical Commission, 2007.
  7. IEC 61869-2:2012, Instrument Transformers — Part 2: Additional Requirements for Current Transformers. Geneva: International Electrotechnical Commission, 2012.
  8. Warrington, A.R.C., “Reactance Relays Negligibly Affected by Arc Impedance,” Electrical World, September 1931.

Content drafted with AI assistance and validated by the author based on 30 years of experience in the Power Quality and Power Systems field.

Scroll to Top