Parpadeo Welding Loads Filtro armónico activo EN 50160 · CEI 61000-4-15 Bélgica

Active Harmonic Filter Reduces Flicker from Radiator Production — Belgium

Fuente: Los filtros activos de armónicos (manufacturer case study) · IPQDF Case Study Series · Flicker · Commentary: Denis Ruest, M.Sc. (Applied), P.Eng. (ret.)
Case at a Glance
FacilityRadiator factory — 55,000 , Bélgica. Six production lines, ~5,000 radiators/day
Disturbing loadsPresses, seam welding machines, spot welding machines — intermittent high-power loads
Flicker beforePst peaks reaching 1.6 — measured 2009
Utility limit demandedPst 95th percentile ≤ 0.7 — EN 50160 / IEC 61000-3-7 framework
SoluciónSix Active Harmonic Filter (AHF) units — 2.1 MVAr total continuous reactive compensation
Flicker afterPst consistently below 0.63 — independently verified
Reduction achievedPst reduced by more than 60% — from 1.6 to below 0.63
Side effectStabilised production environment — voltage fluctuations reduced across all six lines simultaneously

01 Context — Flicker from Industrial Welding

Flicker — the perceptible variation in light output caused by rapid voltage fluctuations — is one of the most neighbour-sensitive power quality problems in industrial environments. Unlike harmonics, which affect equipment directly, flicker is primarily a human perception problem: the voltage fluctuations caused by an industrial process can cause visible light modulation in the homes and offices of other customers connected to the same distribution network, even when those customersown equipment is entirely non-disturbing.

Welding processes are among the most prolific flicker sources in industry. Resistance spot welders and seam welders draw large, repetitive reactive current pulses — each weld pulse draws thousands of amperes for a fraction of a second, creating a voltage dip at the point of common coupling that modulates the supply voltage at a rate determined by the welding repetition rate. When the repetition rate falls in the range of 1–15 Hz — the frequency range of peak human visual sensitivity as characterised by the IEC flickermeter — the resulting light modulation can be perceptible to all customers on the same distribution transformer.

The Community Impact Problem

A radiator factory running six welding production lines simultaneously is not just a noise or emission problem for its immediate neighbours — it is a grid-connected disturbance source that affects every customer connected to the same MV/LV transformer. When the local community grows and new customers connect to the same transformer, the flicker margin shrinks — what was previously acceptable becomes non-compliant when the background flicker from other sources increases. This is exactly what happened here: community expansion forced the utility to tighten the flicker emission limit, making previously tolerated emissions unacceptable.

02 Problem — Pst 1.6 Against a Limit of 0.7

The radiator factory in Belgium — a 55,000 m² facility producing approximately 5,000 radiators per day across six production lines — had a load mix that was inherently demanding from a power quality perspective. Presses, seam welding machines, and spot welding machines operated simultaneously across all six lines, each drawing large intermittent reactive current pulses that produced significant voltage drops at the feeding substation.

Field measurements in 2009 showed Pst (short-term flicker severity) values with peaks reaching 1.6. The EN 50160 planning limit for flicker at the medium-voltage point of common coupling is typically Pst 0.7 assessed as a 95th-percentile value over a one-week observation period. The factory was exceeding this limit by a factor of more than 2 at peak conditions — causing visible light flicker in neighbouring commercial and residential premises whenever multiple welding lines were operating simultaneously.

Flicker Severity Pst — Before and After AHF Installation 0.0 0.5 1.0 1.5 2.0 Pst valor Pst limit = 0.7 1.6 Before AHF Peak Pst (2009) < 0.63 After AHF Consistent Pst (verified) −60%+
Higo. 1 — Pst before and after AHF installation. The utility demanded Pst 0.7 (red dashed line). Peak measured values in 2009 reached 1.6 — more than twice the limit. After AHF installation, the plant consistently achieves Pst abajo 0.63 regardless of which combination of welding lines is operating.
Why Welding Flicker Is Difficult to Mitigate

The challenge cited in this case —rapidly fluctuating load and many different load patterns— is the fundamental difficulty with welding flicker mitigation. A single welding machine produces a predictable, repetitive flicker signature. Six welding lines operating simultaneously produce a complex, stochastic combination of overlapping current pulses at different repetition rates and phases — the resulting voltage fluctuation at the substation is neither periodic nor predictable from the individual load characteristics alone. A compensation system that works for one operating scenario may be inadequate for another. This is why the AHF response time was specifically cited as a critical requirement: the system must track the actual voltage fluctuation in real time, not a predicted or averaged load profile.

03 Solution — Active Harmonic Filtering at 2.1 MVAr

Why an Active Harmonic Filter — not an SVC or passive filter

The solution chosen was six Active Harmonic Filter (AHF) units providing a total of 2.1 MVAr continuous reactive compensation. The AHF approach was selected over the alternatives — passive LC filters, thyristor-controlled SVCs, or standard power factor correction capacitors — for a specific reason: response time.

  • Passive LC filters — fixed reactive compensation, tuned to specific harmonic frequencies. Cannot respond to the stochastic, multi-pattern load fluctuations of six simultaneous welding lines
  • Thyristor-controlled SVC — updates its firing angle at each half-cycle (8.3 señora en 60 Hz, 10 señora en 50 Hz). For welding loads with pulse durations as short as a few cycles, the SVC response delay means the compensation arrives after the disturbance has already occurred — as described in the IPQDF PQ Overview article on flicker mitigation
  • Filtro armónico activo (AHF) — uses IGBTs switching at high frequency to inject precisely controlled reactive current on a cycle-by-cycle basis. Response time is sub-millisecond — fast enough to track the actual welding current waveform and cancel its reactive component before it can produce a measurable voltage drop at the substation bus

System configuration

The installation consisted of six AHF units — one per production line — each sized for the specific reactive demand of that line. The total installed compensation capacity of 2.1 MVAr continuous reflects the aggregate reactive demand of six simultaneous welding lines at full production. The system operates with fully automatic controls and passive cooling, requiring no regular maintenance and no operator intervention. It can operate completely stand-alone or integrated with the plant’s existing SCADA and monitoring systems.

04 Results — Pst Below 0.63 in All Operating Configurations

After installing the AHF system, the plant consistently achieved Pst values below 0.63 — regardless of how many welding lines were running simultaneously and regardless of the production mix on each line. This is the critical test: the utility’s demand was that the Pst 95th-percentile value not exceed 0.7, and the AHF must achieve this across the full range of operating scenarios, not just under the single worst-case or best-case loading condition.

Independent Verification

The post-installation measurements were conducted by external consultants and approved by the local utility — not measured and reported by the AHF manufacturer alone. This is an important credibility distinction: independently verified flicker measurements provide assurance that the Pst reduction is real, reproducible, and not an artefact of measurement conditions or cherry-picked operating scenarios. The utility accepted these measurements as proof of compliance with the emission limit it had demanded.

The production stability side-effect

Beyond the compliance achievement, the plant gained an unexpected operational benefit: stabilised production voltage across all six lines simultaneously. When welding machines draw large reactive current pulses, the resulting voltage drops not only cause flicker on the external network — they also cause internal voltage variations that can affect the consistency of the welding process itself. By eliminating the reactive current pulses at source, the AHF simultaneously eliminated the internal voltage variations, improving the consistency of the weld quality and reducing the variation in energy delivered per weld cycle. This operational benefit — improved process quality — was a direct consequence of the PQ mitigation, not an intended design objective.

05 Perspectiva de la calidad de la energía

This case study illustrates the community dimension of industrial power quality — a dimension that is easy to overlook when PQ is framed solely as an equipment protection problem. The radiator factory’s welding machines were not malfunctioning. The factory was not experiencing internal production problems from its own flicker. The problem was entirely outward-facing: the voltage fluctuations on the shared distribution network were affecting neighbouring customers who had no connection to the factory’s production process.

From a utility distribution engineering perspective, this is one of the most common and most difficult flicker management scenarios: an existing industrial customer whose loads were acceptable when they connected, but whose flicker emissions exceed planning limits as the community grows and new customers share the same distribution infrastructure. The utility’s options in this scenario are limited — they cannot refuse supply to new customers, they cannot easily reinforce the network to eliminate the coupling between existing customers, and they cannot compel the industrial customer to reduce production. The only viable path is requiring the industrial customer to mitigate their own emissions — which is what happened here.

Referencias

  1. Los filtros activos de armónicos. AHF Reduces Flicker from Radiator Production — Belgium Case Study. Active Harmonic Filters manufacturer publication. Available at IPQDF Case Study Library.
  2. IEC 61000-4-15:2010+AMD1:2012. Electromagnetic compatibility — Part 4-15: Testing and measurement techniques — Flickermeter — Functional and design specifications. IEC, Ginebra.
  3. IEC 61000-3-7:2008. Electromagnetic compatibility — Part 3-7: Limits — Assessment of emission limits for the connection of fluctuating installations to MV, HV y EHV sistemas de energía. IEC, Ginebra.
  4. EN 50160:2010+A3:2019. Voltage characteristics of electricity supplied by public electricity networks. CENELEC, Bruselas.
Fuente & Attribution

This case study is based on a manufacturer case study published by Los filtros activos de armónicos: AHF reduce el parpadeo del radiador Producción. El Pst measurements cited (1.6 before, abajo 0.63 after) were independently verified by external consultants and approved by the local utility.

This case study is presented in summary and commentary form for educational purposes. The PQ Perspective section (Sección 5) and SVG diagram are original IPQDF editorial content by Denis Ruest, M.Sc. (Applied), P.Eng. (ret.). IPQDF does not claim authorship of the original case material.

Desplazarse hacia arriba