Todays industry constantly faces new challenges. When society expands in Herentals, بلجيكا, Henrad was faced with the challenge to reduce their flicker emission level in order to not disturb other industries on the public grid
“Comsys provided the most advanced and “We at Laborelec conducted the reference measurements prior to and after the installation – the solution is approved.” |
||
خلفيةHenrad is a Belgian radiator manufacturer in the Caradan Group. و 55000 square meter factory in Herentals, Belgium consists of six production lines that totally can produce about 5000 علبة التروس يوميا. The production process are presses, لحام التماس لحام البقعة و, the nature of the process is very energy demanding and therefore puts great demands on the power grid. This together created large voltage drops in the feeding substation with the result of to high Pst values which would lead to flashing lights when Eandis, the local utility company, would connect other consumers to the same transformer. تحدطالبت شركة المرافق المحلية ان توقيت المحيط الهادي 95% value must not exceed 0,7. قياس القيم خلال 2009 provided by the well-known Belgian consultancy firm Laborelec showed tops in the Pst equivalent to 1,6. The task was very challenging since it’s a rapidly fluctuating load and also the many different load patterns that could occur since its very high number of welding machines. |
Key benefits | Welding – بصيص:
Flicker level before compensation |
|
Solution –
|
||