Supraharmonics MV Networks LV Networks Cable Aging PLC Interference MDPI Sensors 2024

Supraharmonic Distortion in MV and LV Grids — Four Documented Negative Effects and the Limits Gap

Fonte: Mariscotti & Mingotti — University of Genova & University of Bologna (2024) · IPQDF Case Study Series · Supraharmonics · Commentary: Denis Ruest, Mestrado. (Aplicado), P.Eng. (ret.)
Case at a Glance
Paper typeComprehensive analytical review — University of Genova & University of Bologna, Itália
Frequency range addressedSupraharmonics: 2 kHz – 150 kHz (beyond conventional harmonic analysis)
Four documented effectsPower loss & heating · Dielectric aging · MV cable termination failure · PLC interference
Propagation findingStrong correlation measured between substations 16 km apart — SH propagates over long distances in MV networks
MV/LV transformer transferTransfer ratio 0.5 para 3.0 — some SH components are amplified when crossing from MV to LV
Capacitor interactionInput capacitors of nearby loads attract SH currents — reducing propagation but accelerating capacitor aging and causing premature failures
Regulatory statusNo planning or compatibility limits exist above 9 kHz in distribution network standards — active standardisation gap
FonteMariscotti A, Mingotti A. Sensors 2024, 24(8), 2465. DOI: 10.3390/s24082465. Open access CC BY 4.0.

01 Context — A New Frontier of Network Stress

The conventional power quality framework addresses harmonic distortion up to the 40th order — 2 kHz at 50 Hz. Above 2 kHz, the supraharmonic range (2–150 kHz) was historically considered non-problematic: the power electronic devices of the 1980s and 1990s switched at frequencies below or only slightly above this threshold, and their emissions in the supraharmonic range were modest. This assumption no longer holds.

Modern power electronics — PV inverters, EV carregadores, battery storage converters, and LED drivers — use Silicon Carbide (SiC) and Gallium Nitride (GaN) switching devices at frequencies of 20–100 kHz or higher. These devices place their primary switching energy directly in the supraharmonic range. The result is a rapid and widespread contamination of distribution networks with conducted emissions in a frequency band where no emission limits exist, no measurement standards are adequate, and the negative effects on network assets and connected equipment are only beginning to be systematically documented.

O 2024 paper by Mariscotti and Mingotti at the Universities of Genova and Bologna provides the most comprehensive published analysis of supraharmonic effects on MV and LV distribution networks — covering four distinct negative effect categories, propagation characteristics, transformer transfer behaviour, and the implications for standardisation. It is based on approximately 70 documented references spanning a decade of supraharmonic research.

How This Differs from Classical Harmonics

Supraharmonics are not simplyfaster harmonics— their propagation and aggregation behaviour differs fundamentally from classical harmonics. Classical harmonics (abaixo 2 kHz) are synchronised to the mains frequency, propagate predictably through network impedances, and can be modelled by superposition. Supraharmonics have nearly random phase distribution between devices — they partially cancel when aggregated from multiple sources — but they also create network resonances that can amplify specific frequency components locally. Their time behaviour is intermittent and time-varying, unlike the relatively steady classical harmonic spectrum. These differences require different measurement approaches, different modelling tools, and ultimately different limit frameworks.

02 Four Documented Negative Effects

The study identifies and documents four principal categories of negative effects from supraharmonic distortion on MV and LV network assets and connected equipment:

Effect 1 — Thermal

Power Loss and Heating

At supraharmonic frequencies, skin effect concentrates current on the conductor surface, reducing the effective cross-section and increasing resistance. Cabos, transformer windings, and neutral conductors carrying supraharmonic currents run hotter than their power-frequency loading alone would predict. Standard thermal ratings based on power-frequency current are non-conservative in the presence of significant supraharmonic content. Dielectric losses in cable insulation also increase with frequency — the I²R heating mechanism is compounded by dielectric heating within the insulation material itself.

Effect 2 — Aging

Dielectric Material Aging

Elevated electric field intensity at supraharmonic frequencies accelerates dielectric degradation through two mechanisms: partial discharge events (more likely at high field intensities) and dielectric loss heating. Both mechanisms are accelerated by higher frequency — the number of stress cycles per unit time increases proportionally with frequency. A dielectric material exposed to 50 kHz supraharmonics experiences 1,000 times more electrical stress cycles per second than at 50 Hz. This dramatically accelerates aging in cable insulation, capacitor dielectrics, and transformer insulation — particularly in MV equipment where field intensities are already high.

Effect 3 — Failure

MV Cable Termination Failure

The most severe documented consequence of supraharmonic distortion on MV network assets is failure of cable terminations. MV cable terminations are geometrically complex — the transition from the cable’s controlled electric field geometry to the air-insulated connection involves stress relief components (stress cones, field grading materials) designed for power-frequency operation. Supraharmonic currents produce localised heating and elevated electric field stresses at these terminations that the original design did not account for. The combination of dielectric stress and local heating has caused premature termination failures in MV networks with high renewable energy penetration.

Effect 4 — Communication

PLC Interference

Power line carrier communications — used for smart metering (DLMS/COSEM), demand response, grid control, and EV charging management — operate in the 9–148 kHz frequency range (CENELEC bands A–D). This frequency range overlaps directly with the supraharmonic range. Supraharmonic emissions from PV inverters, EV carregadores, and LED drivers can overwhelm PLC signals, causing metering errors, communication failures in demand response systems, and loss of remote monitoring capability. The circular interference problem in EV charging — where the EV charger’s switching emissions disrupt the PLC communication intended to manage EV charging — is an immediately practical manifestation of this effect.

Supraharmonic Effects — Frequency and Asset Dependency 0 Hz 2 kHz 50 kHz 150 kHz Classical harmonics Supraharmonic range — 2 para 150 kHz Skin effect / heating Dielectric aging MV cable terminations PLC interference 9 kHz 148 kHz No limits above here
Figo. 1 — The four supraharmonic effect categories and their frequency dependence. Skin effect heating applies across the full frequency spectrum but intensifies in the supraharmonic range. Dielectric aging, cable termination failure, and PLC interference are primarily supraharmonic phenomena. The red dashed line marks 2 kHz — the upper limit of existing distribution network emission standards.

03 Propagation — Further Than Expected

One of the most significant and practically important findings in the supraharmonic literature is the long-distance propagation of supraharmonic disturbances in MV networks. A strong correlation was measured between supraharmonic levels at two MV substations 16 km apart — demonstrating that a supraharmonic source at one point in the network can affect equipment at substations several kilometres away. This is far beyond the local neighbourhood coupling that engineers intuitively assume for high-frequency conducted emissions.

The Swedish MV network measurement

Field measurements on a real Swedish MV network with eight feeders — including a small wind farm — confirmed supraharmonic propagation across the entire network. The wind farm’s inverter switching frequencies were detectable at all monitoring points across the eight feeders, with the amplitude varying according to the network impedance at each location. The study also found that larger MV networks have more resonant frequencies but lower resonance peak amplitudes — a network impedance characteristic that affects how supraharmonics propagate and where they are amplified.

The Capacitor Trap Effect

Input capacitors of loads connected near the supraharmonic source act as low-impedance paths at high frequencies — they attract supraharmonic currents that would otherwise propagate further into the network. This localises supraharmonic energy near the source and reduces long-distance propagation, which appears beneficial for distant equipment. The cost is accelerated aging and premature failure of the capacitors themselves — which are now absorbing the energy that would otherwise have spread across the network. This is a classic hidden failure mechanism: the protection of distant equipment comes at the expense of accelerated degradation in nearby equipment, without any visible indicator until the capacitor fails.

Supraharmonic Propagation and Capacitor Trap Effect PV Inverter SH source f_sw = 30 kHz MV distribution feeder Capacitor Attracts SH current → accelerated aging Substation A SH detectable Substation B 16 km away Still correlated! Strong SH correlation measured across 16 km separation — Mariscotti & Mingotti, 2024
Figo. 2 — Supraharmonic propagation along an MV feeder. SH amplitude decreases with distance but remains measurable and correlated at substations 16 km apart. A capacitor near the source acts as a low-impedance trap — reducing propagation but absorbing SH energy that accelerates its own aging. The trade-off is invisible until the capacitor fails prematurely.

04 Transformer Transfer — Some Components Are Amplified

The transfer of supraharmonics through MV/LV distribution transformers is not a simple attenuation process. Measurements of transformer transfer ratios at supraharmonic frequencies show a range of 0.5 para 3.0 — meaning that for some frequency components, the supraharmonic amplitude on the LV side is up to three times higher than on the MV side. Some supraharmonic components are amplified in crossing the transformer.

This amplification occurs due to the complex impedance interactions between the transformer’s leakage inductance, winding capacitances, and the capacitive loads connected to the LV side. At certain frequencies, the transformer and connected LV network form a resonant circuit that amplifies voltage at the resonant frequency. The resonant frequencies depend on the transformer design, the cable lengths, and the capacitance of connected loads — all of which vary with load configuration and feeder layout.

05 The Limits Gap — No Rules Above 9 kHz

The most significant regulatory gap identified by Mariscotti and Mingotti is stark: no planning levels or compatibility limits currently exist in distribution network standards for supraharmonics above 9 kHz. The CENELEC EN 50160 padrão, which defines voltage characteristics for public LV networks, addresses frequency deviation, voltage magnitude, harmonics up to the 25th order, and flicker — but contains no limits for the supraharmonic range. IEC 61000-2-2 addresses compatibility levels for LV networks up to 2 kHz. Above 2 kHz, the only relevant limits are in CISPR standards (above 150 kHz, for EMC) and the narrow CENELEC signalling frequency bands — leaving the entire 9 kHz a 150 kHz window unregulated from a distribution network PQ perspective.

Derived Limits and the Standardisation Process

Mariscotti and Mingotti derive indicative limits for supraharmonic distortion based on the documented effect thresholds — using the same physical reasoning applied to derive harmonic limits from equipment sensitivity data. Their derived limits provide a quantitative framework that did not previously exist in the literature. These limits have been submitted to the ongoing standardisation process at IEC SC 77A WG9, which is actively revising IEC 61000-4-30 to address supraharmonic measurement. Contudo, the gap between documented effects, derived limits, and enforceable standards remains wide — and in the interim, network operators have no regulatory basis for requiring equipment manufacturers to control their supraharmonic emissions.

The absence of limits has two practical consequences for distribution network engineers. Primeiro, there is no objective basis for requiring mitigation when supraharmonic disturbances are identified — making it difficult to compel action from the equipment owner whose device is the source. Segundo, when equipment fails prematurely — a capacitor, a cable termination, a PLC metering system — the connection to supraharmonic disturbance is difficult to establish because no baseline measurements were required, no alarm levels were defined, and no monitoring was in place.

06 Power Quality Perspective

This case study is a companion to CS04 (PV Inverter Supraharmonics) and CS07 (EV Charger Supraharmonics) — it addresses the network-level consequences of the source-level emissions documented in those case studies. CS04 and CS07 characterise what individual devices emit. CS08 documents what happens to the network and its assets when those emissions are present at scale.

From a utility engineering perspective, the MV cable termination failure finding is the most immediately actionable. Cable termination failures in MV networks are expensive — replacement requires switching out the affected cable section, mobilising a jointing crew, and managing customer interruptions. If supraharmonic distortion from renewable energy converters connected to the same MV feeder is contributing to accelerated termination aging, the utility is bearing maintenance and capital costs caused by the behaviour of customer-side equipment, with no regulatory mechanism to attribute those costs or require the source to mitigate its emissions.

Referências

  1. Mariscotti A, Mingotti A. “The Effects of Supraharmonic Distortion in MV and LV AC Grids.Sensors, 24(8), 2465, 2024. DOI: 10.3390/s24082465. Open access CC BY 4.0.
  2. Rönnberg SK, Wahlberg M, Bollen MHJ. “Evaluation of Medium Voltage Network for Propagation of Supraharmonics Resonance.Energies, 14(4), 1093, 2021. DOI: 10.3390/en14041093.
  3. IEC 61000-4-30:2015+AMD1:2021. Electromagnetic compatibility — Part 4-30: Métodos de medição da qualidade da energia. IEC, Genebra. (Under revision by SC 77A WG9 to address supraharmonics.)
  4. IN 50160:2010+A3:2019. Voltage characteristics of electricity supplied by public electricity networks. CENELEC, Bruxelas.
  5. IEC 61000-2-2:2002+AMD1:2017. Electromagnetic compatibility — Compatibility levels for LV supply systems, 0–2 kHz. IEC, Genebra.
  6. ADMIT Project. Accurate Measurement of Distorted Instruments and Transformers. EU-funded research project. Available: admit-project.eu
Fonte & Attribution

Mariscotti A, Mingotti A.The Effects of Supraharmonic Distortion in MV and LV AC Grids.Sensors (MDPI), vôo. 24, não. 8, p. 2465, Abril 2024.
DOI: 10.3390/s24082465  · Full text at PMC → — Open access CC BY 4.0.

This case study is presented in summary and commentary form for educational purposes. SVG diagrams and the PQ Perspective section (Seção 6) are original IPQDF editorial content by Denis Ruest, Mestrado. (Aplicado), P.Eng. (ret.). IPQDF does not claim authorship of the original research.

Role até o topo