EV Charging · PQ Harmonics · Phase Imbalance Residential · LV Distribution Field Measurement

Carregadores de veículos elétricos e qualidade de energia residencial – um estudo de campo de duas semanas

Fonte: Ngaopitakkul — Chulalongkorn University, Bangkok, Tailândia (2025) · IPQDF Case Study Series · EV Charging · Comentário: Denis Ruest, Mestrado. (Aplicado), P.Eng. (ret.)
Visão geral do caso
SiteResidential condominium — Bangkok, Tailândia
Measurement durationTwo weeks of continuous field measurement
EV charger typeSingle-phase Level 2 AC chargers (dominant usage pattern)
Desequilíbrio de tensãoAverage 0.535% · Peak 2.18% during active charging
Current THD during charging15–20% — significant increase over baseline
Corrente neutraSignificant — driven by single-phase loading dominance
Infrastructure conditionRetrofitted — not originally designed for EV charging loads
Descoberta chaveSingle-phase EV charging creates phase imbalance and harmonic injection that existing residential wiring was not designed to handle

01 Contexto e histórico

Electric vehicle adoption is accelerating globally, and with it comes a set of power quality challenges that most residential distribution infrastructure was never designed to handle. This field study by Ngaopitakkul (2025) at Chulalongkorn University examines the PQ impact of EV charger deployment in a real residential condominium in Bangkok, Thailand — a city where rapid EV adoption is outpacing electrical infrastructure upgrades.[1]

The study is particularly relevant because it addresses the most common real-world scenario: retrofitted residential infrastructure with single-phase Level 2 AC chargers installed in individual parking spaces or garages, without coordinated load management. This is not a purpose-built EV facility with balanced three-phase charging and smart load control — it is the existing electrical system of a multi-unit residential building confronted with a new generation of high-power non-linear loads that were not anticipated in the original design.

Why This Case Matters for Distribution Engineers

The challenge EV chargers present to distribution networks is different in character from the industrial harmonic problems that dominate most PQ literature. Industrial harmonic sources are concentrated, predictable, and often subject to utility connection studies. Residential EV chargers are distributed, stochastic, and connected to the low-voltage network at points that were never designed to absorb significant harmonic or unbalanced loads. A utility engineer planning distribution upgrades needs field data from exactly this type of setting.

02 Metodologia de Medição

A two-week continuous field measurement campaign was conducted at the condominium’s electrical distribution panel. The measurement duration is important: EV charging behaviour varies with time of day, day of week, and individual resident patterns. A two-week dataset captures the variability that a single-day or single-event measurement would miss, and provides a statistically meaningful characterisation of the PQ impact under realistic usage conditions.[1]

The following parameters were measured and analysed:

  • Load profiles — current demand versus time, revealing charging patterns
  • Current and voltage waveforms — three-phase RMS values and waveform capture during charging events
  • Phase symmetry — distribution of charging load across the three phases
  • A distorção harmônica — current THD analysis during active charging and at baseline
  • Desequilíbrio de tensão — quantified using the maximum deviation method (SEM definição): maximum deviation of any phase voltage from the three-phase mean, dividido pela média
  • Corrente neutra — magnitude and waveform during charging events

03 Principais conclusões

Measured PQ parameters

Parâmetro Linha de base (no charging) During active EV charging Standard limit Status
Current THD Low — normal residential baseline 15–20% IEEE 519: 5–8% TDD at LV PCC ELEVATED
Desequilíbrio de tensão (média) Abaixo 0.5% 0.535% média IN 50160: ≤ 2% (95% da semana) Within limit
Desequilíbrio de tensão (pico) Abaixo 0.5% 2.18% pico IN 50160: ≤ 2% (95% da semana) AT LIMIT
Corrente neutra Baixo Significantly elevated Not directly limited — sizing risk MONITOR
Phase loading symmetry Approximately balanced Single-phase dominant Balanced loading assumed in design IMBALANCED
Fonte: Ngaopitakkul (2025).[1] Two-week field measurement, Bangkok condominium. Voltage unbalance by NEMA maximum deviation method.

Single-phase charging dominates — the root of the unbalance problem

The most significant behavioural finding was that single-phase charging completely dominated the observed usage patterns. Residents used single-phase Level 2 AC chargers, connected to whichever phase their parking space happened to be served by — without any coordination across phases. The result is a highly unbalanced load that varies with how many residents charge simultaneously and which phase they are on.[1]

This is not a technology limitation of EV chargers — three-phase chargers exist and would distribute the load symmetrically. It is a consequence of how residential EV charging is deployed in practice: individual units, individual chargers, no system-level coordination, connected to whatever single-phase branch is available at the parking level.

The Retrofitted Infrastructure Problem

The condominium’s electrical infrastructure was not originally designed for EV charging loads. In retrofitted buildings, the effects of EV charging are often exacerbated by design limitations: neutral conductors sized for the pre-EV load, distribution panels without spare capacity, and wiring runs that were not engineered for the combination of high current magnitude and significant harmonic content. A building designed today with EV charging in mind would have a fundamentally different electrical architecture — three-phase chargers, managed charging systems, oversized neutrals, and a distribution capacity assessment that includes the EV load from the outset.

04 Technical Analysis

EV chargers as non-linear loads

EV on-board chargers use switched-mode power conversion — the AC supply is rectified and then regulated by a high-frequency switching converter to deliver the required DC current to the battery. This makes the EV charger a non-linear load that draws current in pulses rather than a sinusoid, injecting harmonic currents into the supply network. The dominant harmonic orders depend on the converter topology, but third, fifth, and seventh harmonics are typical for single-phase chargers.[1]

The current THD values of 15–20% measured during charging are consistent with published data for residential Level 2 AC chargers without active power factor correction. Modern chargers with active front-end PFC circuits can achieve THD below 5%, but these are not uniformly deployed in the existing residential EV charging population.

Phase imbalance — the neutral current consequence

When single-phase loads dominate on one or two phases, the three-phase system becomes unbalanced. In a four-wire system, the neutral conductor carries the vector sum of the three phase currents — which under balanced sinusoidal conditions is zero. Under the unbalanced single-phase EV charging conditions observed in this study, the neutral current became significant, creating thermal loading on a conductor that was sized for a much smaller current. This is the identical mechanism to the triplen harmonic neutral overloading discussed in hospital PQ case studies — different root cause, same consequence for the neutral conductor.

Voltage unbalance — peak at EN 50160 limite

The average voltage unbalance of 0.535% is well within the EN 50160 limit of 2%. Contudo, the peak of 2.18% during simultaneous charging events on the same phase approaches and momentarily exceeds the limit. For the utility engineer, this is important: IN 50160 a conformidade é avaliada como uma estatística do percentil 95 durante um período de observação de uma semana – um único evento de pico durante uma noite não constitui por si só não conformidade. Mas sinaliza que à medida que a penetração de VE aumenta no edifício, o desequilíbrio de pico aumentará proporcionalmente, e a distribuição estatística se deslocará em direção ao limite.

05 Recomendações

The study identifies the following engineering measures for EV-ready residential systems:[1]

  • Three-phase EV chargers — distribute the charging current symmetrically across all three phases, eliminating the single-phase imbalance problem at source. Appropriate for new installations and major retrofits
  • Coordinated load management (smart charging) — control charging schedules to avoid simultaneous peak demand on the same phase, reduce peak current, and allow time-of-use management. Requires a building energy management system and charger communication capability
  • Phase assignment planning — for single-phase charger installations, deliberately assign chargers to alternate phases across the building to balance the load. Requires inventory of phase assignments at all parking spaces
  • Neutral conductor assessment — review and upsize neutral conductors where single-phase EV charging loads are concentrated. The neutral conductor in a pre-EV building was sized for a balanced load assumption that no longer holds
  • Filtragem harmônica ativa — if the charger population cannot be replaced with PFC-equipped units, a central active harmonic filter at the distribution panel can reduce THD to acceptable levels
  • Distribution capacity study before deployment — any residential building adding EV charging should conduct a load flow and PQ impact study before installing chargers, not after problems appear
The Simplest Immediate Mitigation

Antes de qualquer despesa de capital, a mitigação mais imediata e de custo zero é o planejamento de atribuição de fases. Auditar quais vagas de estacionamento são atendidas por qual fase e atribuir deliberadamente novas conexões de carregador EV à fase menos carregada não custa nada e reduz diretamente o desequilíbrio de pico. Não resolverá o problema harmônico, mas aborda a causa dominante da sobrecarga da corrente neutra e do desequilíbrio de tensão sem nenhum custo de capital.

06 Perspectiva de qualidade de energia

Este estudo de caso representa uma classe de problemas de QP que só crescerá em frequência e gravidade na próxima década: o retrofit de novas cargas não lineares de alta potência em infraestrutura de distribuição que foi projetada para um perfil de carga completamente diferente. EV carregadores, heat pumps, and battery storage systems are all being connected to residential and commercial buildings whose electrical systems were designed for incandescent lighting, resistive heating, and linear motor loads.

From a utility distribution planning perspective, the most important finding in this study is not the individual building numbers — 15–20% THD, 2.18% peak unbalance. These are manageable at a single-building scale. The planning concern is the aggregate: when a significant fraction of homes and condominiums on the same LV feeder deploy single-phase EV chargers with uncoordinated charging, the feeder-level unbalance and harmonic distortion can reach levels that affect all customers on the feeder, not only the EV charging buildings.

Referências

  1. Ngaopitakkul A. “Evaluating Effects of Electric Vehicle Chargers on Residential Power Infrastructure.Applied Sciences, vôo. 15, não. 11, p. 5997, 2025. DOI: 10.3390/app15115997. Acesso aberto sob CC BY 3.0.
  2. IN 50160:2010+A3:2019. Características de tensão da eletricidade fornecida por redes elétricas públicas. CENELEC, Bruxelas.
  3. IEEE Std 519-2022. Padrão IEEE para Controle Harmônico em Sistemas Elétricos de Potência. IEEE, Nova Iorque, Nova Iorque, 2022.
  4. NÃO MG-1-2021. Motors and Generators — Voltage Unbalance Definition. Associação Nacional de Fabricantes Elétricos, Rosslyn, VA.
Fonte & Atribuição

Ngaopitakkul A.Evaluating Effects of Electric Vehicle Chargers on Residential Power Infrastructure.Applied Sciences, 15(11), 5997, 2025.
DOI: 10.3390/app15115997  · Leia o artigo original em MDPI →