ADFは、動的なテストベッドを向上させます (コムシスAB)

Within a major leading edge manufacturing company, a test bed put extreme demands on the power supply network. このケーススタディで, an ADF installation compensates harmonics up to the 100th order resulting in significant reduction of notching.

背景

The development department within a major european plant owns several test benches to test certain components in their products during the development phase. Different test conditions can be programmed, giving the test bench extremely dynamic properties.

挑戦

Two parts of the test bench are connected to the same transformer. The load is very dynamic and the amplitude of the load current can change from zero to its maximum in approximately 100 MS. Both parts of the test bench could not be run at the same time, because of the high harmonic disturbances and voltage notches up to 25 %. Apart from exceeding the limits in EN61000-2-4, this also caused serious delay in the testing facility.

ソリューション -
ADF Active Filters from Comsys

The owner of the facility installed equipment from コムシスAB to compensate the disturbances. Two ADF P300W-200/480 and one ADF P200W-100/480 were installed to compensate all frequencies up to the 100th harmonic order. ザ ADF P300 series can be used to compensate lower harmonics and the ADF P200 series can compensate the higher order harmonics and interharmonics. ザ ADFのアクティブ·フィルタ units were configured to share the load, the P200 working on higher orders only. The result was extremely short response times and much lowered disturbances of the load.

結果

Voltage notches could be reduced to 10 % and all harmonics could be lowered to the requested level regarding to EN61000-2-4. The usage of both test benches is now possible and surrounding problems that had been linked to the poor power quality where solved.

前:

  • 現在では非常に高い歪み
  • 激しい電圧ノッチをメモ

dynamic before

後に:

  • 電圧と電流の両方で非常に低歪み
  • 減少ノッチに注意してください

dynamic after

コムシスAB•イデオンサイエンスパーク•SE-223 70 ルンド•スウェーデン
電話: +46 46 286 35 00 •ファックス: +46 46 286 35 05
電子メール:info@comsys.se