ADFは、動的なテストベッドを向上させます (コムシスAB)

Within a major leading edge manufacturing company, a test bed put extreme demands on the power supply network. このケーススタディで, an ADF installation compensates harmonics up to the 100th order resulting in significant reduction of notching.

背景

The development department within a major european plant owns several test benches to test certain components in their products during the development phase. Different test conditions can be programmed, giving the test bench extremely dynamic properties.

挑戦

Two parts of the test bench are connected to the same transformer. The load is very dynamic and the amplitude of the load current can change from zero to its maximum in approximately 100 MS. Both parts of the test bench could not be run at the same time, because of the high harmonic disturbances and voltage notches up to 25 %. EN61000-2-4 の制限を超えることは別として, これにより、検査施設に重大な遅れが生じました.

ソリューション -
Comsys の ADF アクティブ フィルター

施設の所有者が設備を設置しました コムシスAB 乱れを補うために. 2 台の ADF P300W-200/480 と 1 台の ADF P200W-100/480 を取り付けて、100 次高調波までのすべての周波数を補償しました. ザ ADF P300 シリーズを使用すると、低次高調波を補償できます。 ADF P200 シリーズは高次高調波と次数間高調波を補償できます. ザ ADFのアクティブ·フィルタ ユニットは負荷を共有するように構成されています, P200 は高次でのみ動作します. その結果、応答時間が非常に短くなり、負荷の外乱が大幅に減少しました。.

結果

電圧ノッチは次のように削減できます。 10 % すべての高調波は EN61000-2-4 に関する要求レベルまで下げることができました。. 両方のテストベンチの使用が可能になり、電源品質の低下に関連していた周囲の問題が解決されました。.

前:

  • 現在では非常に高い歪み
  • 激しい電圧ノッチをメモ

ダイナミックな前

後に:

  • 電圧と電流の両方で非常に低歪み
  • 減少ノッチに注意してください

ダイナミックな後

コムシスAB•イデオンサイエンスパーク•SE-223 70 ルンド•スウェーデン
電話: +46 46 286 35 00 •ファックス: +46 46 286 35 05
電子メール:info@comsys.se