Interharmonics — The Power Quality Disturbance That Doesn’t Show Up on Standard Harmonic Analysers

Interharmonics — frequency components that are not integer multiples of the fundamental (उदा.. 75 हर्ट्ज, 130 Hz on a 50 Hz system) — are produced by PV inverters, wind turbines, EV chargers, cycloconverters, and HVDC links. Their most dangerous effect: an interharmonic at 58 Hz creates an 8 Hz beat frequency — squarely in the range of peak human visual sensitivity. Field case: simultaneous PV + EV charger + microwave on one LV circuit produces stochastic interharmonics causing light flicker. Standard IEC 61000-4-7 analysers cannot correctly characterise them.