Consolidated Edison Company of New York is a long time user of Dranetz power quality monitoring systems and sister company Electrotek Concepts software and services. Dranetz سلسلة الظهور (61000) and Enhanced Power Quality, EPQ DataNodes) and legacy power quality instruments (8010 PQNode) are deployed throughout their network collecting needed data for PQ assessment. Electrotek’s PQView software, which is seamlessly integrated with the Encore System, provides database management, reporting and advanced statistical analysis. PQView’s Fault Analysis Modules identify and characterize faults, providing location information. Alarms are sent to operators who dispatch crews for repair, reducing the time to locate faults by hours.
تم استخدام نظام تحديد موقع خطأ التوزيع التلقائي في شركة Consolidated Edison Company في نيويورك لأول مرة خلال ربيع عام 2005. يتضمن شاشات مراقبة جودة الطاقة, مرحلات المعالجات الدقيقة, تطبيقات قواعد البيانات, نماذج حديثة لدوائر التوزيع, ونظام المعلومات الجغرافية (نظم المعلومات الجغرافية) قواعد البيانات من أجل توفير التعرف التلقائي على أخطاء التوزيع وتقدير موقع الخطأ. لقد أصبح النظام أداة لا غنى عنها لتحديد موقع الأعطال بسرعة ودقة في نظام توزيع شبكة Con Edison.
يستخدم نظام موقع الخطأ القياسات المسجلة بواسطة شاشات Encore Series PQ الموجودة في محطات التوزيع الفرعية. يتم تنزيل هذه القياسات تلقائيًا بواسطة برنامج Encore Series الذي يدير نظام مراقبة جودة الطاقة. Fault data is automatically acquired by PQView software and stored in its relational database. Calculations on these measurements estimate the reactance from the substation to the fault. The calculations are based on phasor measurements derived from the voltage and current samples and calibration constants based on previous fault data and known locations. The result of these calculations is an estimated “reactance to fault,” or XTF. The XTF values are compared with feeder models that estimate the positive-sequence impedance between substation and feeder structures. The estimated locations can be viewed in tabular format on the corporate intranet and can be displayed graphically using maps derived from a GIS database. The estimations for fault location typically are available on the company intranet approximately ten minutes after the fault’s occurrence. The estimates are accurate to within 10% of the total number of feeder structures, for about 80% of the single-phase faults measured in the system.

Each Dranetz power quality monitor records voltage and current at the output of a transformer in parallel with other transformers that together supply up to thirty underground network distribution feeders.

Example of a single phase fault on Con Edison network estimated to be j0.97 ohms downline from monitored substation

Example Summary Page for Faults Measured in a Network

Example Map Display of Estimated Fault Location