공장에서 정전 (HIOKI)

설정

모니터링 위치 : A factory in Southeast Asia, 1-2 단계 선, 100V 회로

문제

The power supply is damaged

분석

1. 전압 변동

공장에서 정전  1

The following power characteristics were concluded from analyzing this 2-week voltage fluctuation graph.

공장에서 정전  2

불행하게도, sufficient event data was not recorded in No. 1 and No. 2, so that detailed analysis was not possible. The important point to note is that a large voltage fluctuation occurred between 9 p.m. 과 9 a.m. everyday (아니. 3), and the fluctuation was large at about 50V (between 75Vrms and 125Vrms).

2. Event Data

The voltage dip (instantaneous voltage drop) occurred frequently at night. Only 5 voltage dips were detectable in a 1s period. All voltage dip situations demonstrated the same tendency. This is the analysis of one voltage dip event.

  1. When the depth of the voltage dip reaches 90Vrms, the power supply is switched from the commercial supply to the UPS.
  2. When the power supply is switched to the UPS, 전압 RMS 값이 116Vrms로 증가합니다. (125Vrms 최대).
  3. UPS 전원의 전압 파형은 사인파에서 구형파로 변경됩니다..
  4. 사각파가 약 1.25초 동안 지속됩니다..
  5. 전원 공급 장치는 나중에 UPS에서 상용 공급 장치로 변경됩니다.. 이 전환 시, 전압이 78Vrms로 떨어집니다. (75Vrms 최소() 짧은 기간 동안.

공장에서 정전  3 공장에서 정전  4 공장에서 정전  5

3. 분석 요약

  1. 야간에 전원 품질 저하가 자주 발생 (9 p.m. 에 9 오전.)
  2. 전력 품질 저하 현상은 전압이 떨어지면 시작됩니다..
  3. 상용전원에서 UPS로 전환시 전압강하로 인한 oltage swell 발생.
  4. 상용전원이 복구되어 전원이 UPS에서 상용전원으로 전환될 때 전압강하가 발생합니다..

4. 대책

1) 기본 솔루션
전압 강하로 인해 UPS로 자주 전환하는 것은 바람직하지 않습니다.. 전압 강하 및 팽창으로 인해 장비에 과부하 전류가 흐르는 것으로 나타남. 이 문제를 반드시 해결하려면, 전압 강하 발생을 방지하려면 전원 공급 장치를 안정화해야 합니다..
2) 대체 솔루션
UPS는 "대기 전원 시스템"으로 사용됩니다. (SPS)". 비용이 더 많이 들지만 "온라인 UPS 시스템"으로 변경함으로써, UPS 전환 중에 급강하 및 급상승을 줄일 수 있습니다..

JIS C4411-3에 규정된 UPS의 종류는 다음과 같습니다., 2004 기준.

공장에서 정전  6

 

출처 : 전력 품질 측정을위한 가이드 북, HIOKI E.E. 법인

 

 