모니터링 위치 : A factory in Southeast Asia, 1-2 단계 선, 100V 회로
문제
The power supply is damaged
분석
1. 전압 변동
The following power characteristics were concluded from analyzing this 2-week voltage fluctuation graph.
불행하게도, sufficient event data was not recorded in No. 1 and No. 2, so that detailed analysis was not possible. The important point to note is that a large voltage fluctuation occurred between 9 p.m. 과 9 a.m. everyday (아니. 3), and the fluctuation was large at about 50V (between 75Vrms and 125Vrms).
2. Event Data
The voltage dip (instantaneous voltage drop) occurred frequently at night. Only 5 voltage dips were detectable in a 1s period. All voltage dip situations demonstrated the same tendency. This is the analysis of one voltage dip event.
- When the depth of the voltage dip reaches 90Vrms, the power supply is switched from the commercial supply to the UPS.
- When the power supply is switched to the UPS, 전압 RMS 값이 116Vrms로 증가합니다. (125Vrms 최대).
- UPS 전원의 전압 파형은 사인파에서 구형파로 변경됩니다..
- 사각파가 약 1.25초 동안 지속됩니다..
- 전원 공급 장치는 나중에 UPS에서 상용 공급 장치로 변경됩니다.. 이 전환 시, 전압이 78Vrms로 떨어집니다. (75Vrms 최소() 짧은 기간 동안.
3. 분석 요약
- 야간에 전원 품질 저하가 자주 발생 (9 p.m. 에 9 오전.)
- 전력 품질 저하 현상은 전압이 떨어지면 시작됩니다..
- 상용전원에서 UPS로 전환시 전압강하로 인한 oltage swell 발생.
- 상용전원이 복구되어 전원이 UPS에서 상용전원으로 전환될 때 전압강하가 발생합니다..
4. 대책
1) 기본 솔루션
전압 강하로 인해 UPS로 자주 전환하는 것은 바람직하지 않습니다.. 전압 강하 및 팽창으로 인해 장비에 과부하 전류가 흐르는 것으로 나타남. 이 문제를 반드시 해결하려면, 전압 강하 발생을 방지하려면 전원 공급 장치를 안정화해야 합니다..
2) 대체 솔루션
UPS는 "대기 전원 시스템"으로 사용됩니다. (SPS)". 비용이 더 많이 들지만 "온라인 UPS 시스템"으로 변경함으로써, UPS 전환 중에 급강하 및 급상승을 줄일 수 있습니다..
JIS C4411-3에 규정된 UPS의 종류는 다음과 같습니다., 2004 기준.
출처 : 전력 품질 측정을위한 가이드 북, HIOKI E.E. 법인